Jpn. J. Infect. Dis., 53, 206-207, 2000

To see an article, click this [PDF] link.

Laboratory and Epidemiology Communications

Monitoring for Airborne Particles during and after Surgical Operations on Tuberculosis Patients

Kiminori Toyooka, Hiroichi Kishi, Yoshikazu Naiki, Etsuko Hino, Toshiko Suzuki, Morito Sumiya, Koichiro Kudo, Oichirou Kobori, Yoshio Yazaki and Teruo Kirikae*

International Medical Center of Japan,
Toyama 1-21-1, Shinjuku-ku, Tokyo 162-8655

Communicated by Hiroshi Yoshikura

(Accepted October 23, 2000)

Ventilation control is essential for preventing nosocomial transmission of airborne infections, such as tuberculosis (1). A practical method to assess ventilation systems in health-care facilities involves monitoring airborne particles of a certain range in size using particle counters (2).

The monitoring was conducted in operating rooms (OR1 and OR8) in a hospital with 925 beds before, during, and after operations on patients who had tuberculosis. The OR1 and OR8 were of the same size: 91.8 m3 (6 m wide by 6 m deep by 2.55 m high). The OR8 had an anteroom of 38.25 m3 (5 m wide by 3 m deep by 2.55 m high). Both operating rooms were equipped with the same single-pass ventilation system in which, after air passes through the room, 100% of that air was exhausted to the outside. Two air-supply vents were located in the ceiling and four air-exhaust vents were near the floor in each corner. The vents were fitted with high-efficiency particulate air (HEPA) filters for air cleaning. The air supply and exhaust volumes were 1,357 and 1,537 m3/h for OR1, 2,079 and 2,829 m3/h for OR8, and 576 and 1,323 m3/h for the anteroom of OR8, respectively. Airborne particles with †0.3, †0.5, †1.0, †2.0, and †5.0 ƒÊm diameter in OR1 and OR8 were simultaneously counted using a laser particle counter (KC-03A1, Rion Co., Tokyo) placed on a stand 1 m in height, 50 cm from the wall, 50 cm left from an exhaust vent that was on the side of the corridor but opposite the door.

The fluctuation in airborne particles in an operating room is shown in Figure 1. The ventilator was turned on at 7:20 in the morning. Two nurses entered and left the room from 8:30 to 9:00 for preparation. The entrance time of a patient with three doctors and two nurses was 9:00, and the leaving time was 15:31. After leaving, no one was allowed to enter the room until the end of the monitoring period. Before the ventilator was turned on, little fluctuation in numbers of particles was observed. Particles of †0.3 and †0.5 ƒÊm diameter were 2 - 6 x 103/ft3 (7 - 20 x 104/m3) and 2 - 6 x 102/ft3 (7 - 20 x 103/m3), respectively, and larger particles were few. After the ventilator was turned on, the numbers of small particles immediately decreased. When the patient entered, numbers of particles increased and remained high with sharp fluctuations, i.e., 102 - 103/ft3 for †0.3 ƒÊm, 10 - 103/ft3 for †0.5 ƒÊm and †1 ƒÊm, during the operation. After the patient left, the number of particles decreased rapidly by a factor of 102/ft3 for †0.3 ƒÊm, 10/ft3 for †0.5 ƒÊm, and <10/ft3 for †1 ƒÊm. These data confirmed the efficacy of the ventilation system in the operating rooms and suggested that the short-term ventilation following the operation effectively removed contaminated air.

To assess the efficacy of operating room ventilation following operations, we monitored airborne particles after two operations each in two operating rooms. In OR1, it took about 15 and 16 min, respectively, for the airborne particles to decrease to the backgrounds levels (Fig. 2 A, B). In OR8, it took 36 and 18 min (Fig. 2 C, D). These data indicate that monitoring for airborne particles during and after surgical operations is a practical method to evaluate the potency of ventilation system in operating rooms.

REFERENCES

  1. Centers for Disease Control and Prevention (1994): Guidelines for preventing the transmission of Mycobacterium tuberculosis in health-care facilities. Morbid. Mortal. Wkly. Rep., 43, RR-13, 1-132.
  2. Nevins, R.G. (1971): Environmental control of health-care facilities. CRC Crit. Rev. Bioeng., 1, 217-239.